Equipment Repair Directory

Extinguisher Placement & Inspection Log

An extinguisher only helps if it is close, charged and the right type. This log sets placement by walking distance, schedules monthly checks, and records yearly service so every unit is accounted for.

Why it matters

Fires double in size quickly, so a unit that is 100 feet and a locked door away may as well be missing. Placement standards use travel distance, hazard type and rating, and local rules differ. Check NFPA guidance, OSHA and your insurer, and train everyone using the shop on the PASS steps.

Step by step

  1. Sketch the shop and mark fuel, welding, battery charging, parts washer and exits, since those are your higher-hazard spots.
  2. Match type to hazard: ordinary combustibles, flammable liquids and energized electrical equipment, or use a multipurpose rated unit.
  3. Place units so a worker walks no more than about 75 feet to reach one for ordinary combustibles, and about 50 feet for flammable liquids.
  4. Mount each unit visibly near an exit path, with the top typically no higher than 5 feet for lighter units and the handle clear.
  5. Every month, check the gauge in the green, pin and seal intact, no damage, and initial the tag or log.
  6. Have a qualified service company do the yearly maintenance and any required pressure test, and replace or recharge any used unit.

Worked example

Illustrative: A shop is 120 ft long and 40 ft wide, with units on one long wall. One unit at the middle leaves the far corner 60 + 40 = 100 ft away, over the 75 ft rule. Two units placed 30 ft from each end cover the farthest point at 30 + 40 = 70 ft. The fuel tank is 35 ft from one unit, inside the 50 ft limit. Two units checked monthly make 2 x 12 = 24 checks a year.

Printable worksheet: extinguisher placement and inspection log

  • Shop length and width: ______ ft x ______ ft
  • Unit number, type and location: ______ / ____________ / ____________
  • Walking distance to farthest point: ______ ft (limit about 75 or 50)
  • Monthly check date, gauge in green, pin and seal intact: ______ / ______
  • Mount height to top ______ ft ; clear of clutter (yes or no): ______
  • Annual service date and company: ____________
  • Units used or recharged, and replaced on (date): ______

Common mistakes

  • Measuring distance in a straight line when the walk goes around a tractor or workbench.
  • Hanging the only unit next to the hazard, so a fire there blocks access.
  • Marking checks done without reading the gauge or looking for a broken pin seal.
  • Assuming a small kitchen unit suits a fuel or welding area.

Frequently asked questions

What does PASS stand for?

Pull the pin, aim at the base of the fire, squeeze the handle and sweep side to side. Leave at once if the fire grows, the room fills with smoke or your exit is at risk, and call emergency services.

How many units do I need?

It depends on floor area, hazards and local rules. Start with distance and type, then ask your insurer, fire department or fire marshal what they require for your building.

Can I recharge it myself?

Used or low units should go to a qualified service company, since pressure and agent must be right. A unit that has been partly discharged is not reliable, so replace it rather than guess.

Official sources

Educational only. Follow the operator manual, manufacturer service intervals, label or SDS and OSHA rules. State repair and parts directory.